LSI & RSI Expert Water Chemistry Calculator

🧪 LSI & RSI Expert Calculator

Complete Water Chemistry Analysis • Auto Calculate • Treatment Guide

Measured water pH (0 – 14) Enter a valid pH between 0 and 14
Water temperature Enter a valid temperature
mg/L as CaCO₃ Enter a positive value
mg/L as CaCO₃ Enter a positive value
µS/cm (micromhos/cm) Enter a positive conductivity value
Auto-sets the conversion factor
0.64
Adjust manually (0.50 – 1.00)
Estimated TDS: — mg/L
Select a water type above or use the slider for custom factor.
LANGELIER SATURATION INDEX
Live
—
Enter values to begin
−2 −1 0 +1 +2

LSI

—
—

RSI

—
—

CaCO₃ Saturation

—
—
0% 50% 100% 150% 200%+
Conductivity—
Water Type—
Conv. Factor—
Derived TDS—
A (TDS factor)—(log₁₀TDS − 1) / 10
B (Temp factor)—−13.12·log₁₀(T+273) + 34.55
C (Ca²⁺ factor)—log₁₀[Ca] − 0.4
D (Alk factor)—log₁₀[Alk]
pHs (saturation pH)—
RSI = 2pHs − pH—
LSI = pH − pHs —
LSI < −0.30 CaCO₃ undersaturated
Corrosive tendency
−0.30 ≤ LSI ≤ +0.30 Near saturation
Approximately balanced
LSI > +0.30 Scale-forming tendency
Protective film possible